Description
The City of Salina is upgrading its water distribution system under Project 26017, replacing aging water mains and associated infrastructure. The addendum clarifies several construction details, including valveâbox removal depths, topsoil requirements, concrete coring procedures, shoring responsibilities, and pipe pressure class specifications. Contractors may use either openâcut or directionalâboring methods (with two mandated bores under the storm sewer) and must adhere to specific material standards for service lines and meter pits. No new work items are added; the addendum only amends general notes and deletes an outdated pipeâthickness clause.
⢠Valveâbox removal: minimum 24 in depth; 3Ⲡà 3Ⲡroadway removal if in roadways.
⢠Topsoil: at least 6 in of commercialâgrade topsoil at all excavations.
⢠Concrete coring & replacement: detailed repairs for roadway, driveway, and sidewalk sections.
⢠Shoring: contractor must provide all shoring per OSHA requirements.
⢠Pipe pressure class: Class 350 for ⤠12âł ductileâiron pipe; Class 250 for ⼠16âł.
⢠Meterâpit & serviceâline details: specific pit dimensions, copper material required, adapters for subâ1âł meters to be supplied by contractor.